Skip navigation

Procedure: Managing fume exhaust system

Purpose

The purpose of this procedure is to define the requirements for managing fume exhaust systems in laboratories at the Australian National University (University). The managing fume exhaust system procedure ensures that legal and other obligations of the Work Health and Safety Act, 2011 (Cth), and the Work Health and Safety Regulations, 2011 (Cth) are defined for managing the health and safety of all workers. This procedure is linked to the University’s Work health and safety (WHS) policy and is one of the safe work procedures within the WHS Management System.

Definitions

Filter is a device for the removal of contaminants from the air stream. High Efficiency Particulate Air (HEPA) filters are used to remove dust, fine particulates, and biological agents. Activated Carbon filters are used for the removal of organic vapours.

Fume cupboard is a five-sided exhaust hood for the capture, dilution and exhausting of laboratory emissions, especially those that are hazardous. The efficiency and safety of a fume cupboard depends upon the smooth entry of air, effective containment and scavenging of the emission from the chamber, and its safe and remote dispersal into the atmosphere. The effectiveness and efficiency of a fume cupboard also depends upon its location, laboratory ventilation and nearby turbulence, and if fitted, the cleaning system (e.g. scrubber or filter).

Fume exhaust system is any system comprising of a capturing hood, duct, fan and exhaust outlet used for the removal of hazardous or noxious gases, vapours, mists, dusts and other aerosols from a work environment, store or apparatus.

Fume hood is a device mounted above a work area to receive or capture an emission. It provides little or no enclosure of the workspace and is therefore unable to attain the containment of a fume cupboard.

Inspector is a person responsible for the testing, inspection or maintenance of a fume exhaust system.

Laminar (air) – flow is a non-turbulent airstream of constant velocity, substantially uniform over its cross-sectional flow.

Local area refers to a College, Research School or Service Division of the University.

Logbook contains information regarding the type of cupboard, safe operation, design characteristics, cleaning system, maintenance checks and repairs and performance test results. Logbooks are kept with the fume exhaust system. An example logbook is accessible via the Policy Library. A clear plastic sleeve fixed to the exhaust system (e.g. fume cupboard face) with loose-leaf sheets is acceptable as a logbook.

Make-up air is the air needed to replace the air that is removed from the room by the fume exhaust system.

Operation is a task, process, mechanism or equipment capable of generating a hazardous or noxious emission.

Sash is the transparent safety screen between the work chamber and the operator. It can be adjusted vertically (or horizontally) to vary the size of the working aperture.

Scrubber is a wet air cleaning technique or equipment for the removal of water soluble contaminants (e.g. acid gases, biological agents) and some dusts from the exhausted air. In general, they involve spraying an aqueous solution onto a coarse filter material (increasing the water to gas contact area) within the airflow. The contaminant adheres to or dissolves into the aqueous solution where it is physically or chemically removed from the air stream.

Services are the supplies (of lighting, electricity, water, and compressed gases etc.) that are available in the fume cupboard.

Site contact is the person a contractor liaises with to get access to an area and to inform of any deficiencies. This person is the business, laboratory or workshop manager or the safety officer.

A Worker is anyone who carries out work for the University. A worker includes staff, volunteers, contractor, students and visitors at the University.

Procedure

Scope

  1. This is the University procedure for approving, purchasing, installing, using, and maintaining fume exhaust systems. A fume exhaust system is any system with a capturing hood, duct, fan and exhaust outlet that removes hazardous or harmful gases, vapours, mists, dusts and other aerosols from a work environment, store or apparatus to reduce potential hazards such as accumulating explosive gases.
  2. The University has classified fume exhaust systems according to Australian Standards (AS)/ New Zealand Standards (NZS) 2243.8:2014.Refer to Table 1.

Emergency information

  1. Direct emergency queries should be made to the local area management then Work Environment Group (WEG), HR Division (x52193). Local area management is responsible for coordinating any Emergency Services response. After-hours, contact ANU Security (x52249).

Responsibilities

  1. Workers are responsible for using the correct type of fume cupboard for the work, process, or activity they wish to undertake.
    For direct enquiries on the suitability of the system contact the Building Safety Officer, Work Health Safety (WHS) Committee or the WHS Officer;
  • operating the system safely as with manufacturer’s requirements, refer to The safe use of fume cupboard guideline;
  • designing and setting up their laboratory experiment to ensure they minimise any hazardous emissions and that any release occurs in a controlled manner;
  • cleaning the workspace before any maintenance;
  • updating the logbook;
  • reporting any faults or incidents;
  • regularly checking for laboratory standards; and
  • lowering the sash when not working at the fume cupboard.

Note: A variable speed fume cupboard works most efficiently when the sash is down, reducing the tempered air being exhausted, saving electricity associated with heating and cooling costs and hence reducing greenhouse gas emissions. Not only will lowering sashes save money (approximately $400,000 a year across the University), laboratories are more comfortable and safe.

  1. The responsible person for the local area or delegated representative is responsible for:
  • ensuring the operation of the scrubber (if fitted) is checked in accordance with the manufacturer’s requirements (or at least twice annually) to ensure the scrubber is functioning correctly;
  • updating the logbook;
  • carrying out random checks on chemical usage to ensure that it complies with the fume cupboard grading;
  • consulting the WEG Representative (via whs@anu.edu.au) on proposed changes to the location and/or classification of fume exhaust systems; and
  • assisting in the notification of maintenance work to be conducted on fume exhausts systems.
  1. The maintenance contractor is responsible for:
  • conducting general inspections and maintaining the fume exhaust system;
  • updating the logbook after completing any work; and
  • accessing rooftops, roof and ceiling spaces or confined spaces in accordance with the University's policies and procedures.

Note: Standard Safe Operating Procedures are available from the local contact person.

  1. The University (Local area) WHS Officer is responsible for:
  • liaising with the responsible person or delegate representative and WHS Committee on all aspects of the fume exhaust systems;
  • classifying the fume exhaust system, according to the classification system in Appendix 2 of AS/NZS 2243.8:2014;
  • assessing the fume cupboards for upgrade under the Facilities & Services Division upgrade program; and
  • inspecting the system and confirming details of any failed performance test in the event of any dispute.
  1. The Facilities & Services (F&S) Division, is responsible for:
  • liaising with building designers and constructors to ensure they follow this procedure;
  • managing, installing and commissioning new or upgraded fume exhaust systems;
  • responding to maintenance requests;
  • conducting or arranging six-monthly and annual maintenance routines as described in Part 4 of AS/NZS 2243.8: 2014;
  • conducting or arranging yearly checks, including performance tests under AS/NZS 2243.8: 2014;
  • labelling the fume exhaust system with the correct signage; and
  • maintaining the building's ventilation design plans and features.

Fume exhaust system classification

  1. Table 1 describes the various classifications of fume exhaust systems.

Table 1: Classification of fume exhaust systems

Classification

Description

Example

General exhaust system (GP)

Fume exhaust systems other than fume cupboards

These should comply with relevant standards and reduce workplace contaminants below the occupational exposure standard.

Photographic laboratory slot exhaust systems, welders elephant trunk exhaust system, soldering fume extraction system

Ventilated work area (V)

Not a fume cupboard
Used as a ventilated work area. For non-toxic storage and work

A hood over a bench to improve general ventilation

Fume enclosure (FE)

Not a fume cupboard
Used as a ventilated storage area

A ventilated cabinet for the use\storage of low to moderately hazardous materials

Fume cupboard - standard (ST)

Standard fume cupboard

Cupboard manufacture, installation, and air velocities conform to AS 2243.8. Dilution of air should ensure that the discharge complies with the occupational exposure standards.

Laboratory fume cupboard

Fume cupboard – scrubbed (SC)

Scrubbed fume cupboard

Standard fume cupboard fitted with an air-cleaning device. Cupboard manufacture, installation, and air velocities conform to AS 2243.8. Dilution and scrubbing of the air ensures the discharge complies with the occupational exposure standards.

Fume cupboards used in high-volume acid laboratories

Can be used as a standard fume cupboard

Fume cupboard – perchloric (FP)

Perchloric acid fume cupboard

The cupboard is suitable for large volumes of water soluble chemicals as well as perchloric acid\ perchlorates. It incorporates a water wash down facility.

Must be used when handling perchloric acids. Can also be used as a standard fume cupboard or scrubbed cupboard.

Fume cupboard – special purpose (SP)

Special purpose fume cupboard

Cupboard manufacture, installation, and air velocities conform to AS 2243.8. Discharge may be filtered, scrubbed, incinerated or incorporate a wash down facility to meet special requirements.

Downdraft heavy organic vapour\liquid fume cupboards

Care should be taken when using these cupboards for other purposes, as they may not function efficiently

Fume exhaust system approval

  1. Table 2 describes the method for approving and buying a new fume exhaust system or varying an existing unit.

Table 2: Method of approving or buying fume exhaust system

Stage

Who

Description

1

Requesting Officer

Completes a Fume Exhaust System Request Form and Site Plan and sends them to WEG at whs@anu.edu.au.

Note. Use the approved form for all requests for installing a new system or varying an existing unit.

2

Work Environment Group

Inspects the proposed site for suitability.

Checks the exhaust system classification is correct.

Performs any variations in consultation with the Requesting Officer.

Forwards the completed Request Form and Site Plan to F&S with a copy to the local area. Notes the assessment may be performed in consultation with F&S staff and the relevant business, operations, safety, and/or technical staff.

Meets the criteria of AS/NZS 2243.8.

3

Facilities and Services

Checks the requirements and sends a services, construction and special requirements package to the requesting officer.

Advises the relevant officer of services for alternatives and construction materials available for their system.

4

Requesting Officer

Completes the package and returns it to F&S.

5

Facilities and Services

Approves the purchase, sends a copy of the approval to the Requesting Officer and keeps the original documentation.

Contacts the manufacturer or supplier to find out system availability.

Develops the contracts for purchase and installation and sends them to the manufacturer/supplier.

Installation of a fume exhaust system

  1. Table 3 describes the installation and acceptance of the fume exhaust system.

Table 3: Installation and acceptance of fume exhaust system

Stage

Who

Description

1

Facilities and Services

If the installation complies with AS/NZS2243.8, then contacts the manufacturer/supplier and organises the installation of the fume exhaust system.

If the installation does NOT comply with the Australian standard, then contacts WEG to approve the installation of the system.

2

WEG

Assesses compliance issues.

Approves the installation.

Consults with Fire Safety Officer regarding fire detection and suppression, if relevant.

Forwards the approval to Facilities and Services

3

Manufacturer/supplier

Installs the fume exhaust system.

Enters the following details in the system's Logbook: face velocity, smoke capture test, emergency shutdown activation from the fire detector (if fitted),noise level, illuminance, and notes any shortages and compliance issues in the Fume Exhaust System Logbook.

Provides documentation to the local area and F&S for the fume exhaust system, including installation requirements, system specifications (including any fire control measures), commissioning tests,

operator's handbook, maintenance procedures and schedule, instructions in cleaning the system (if fitted), and any special details.

Provides a report on any unusual or conflicting reports to WEG (whs@anu.edu.au).

Provides a report to F&S in the format of AS/NZS 2243.8 (Appendix F).

4

Facilities and Services

If the fume exhaust system is critical to the operation then organises an independent consultant to confirm compliance.

5

Independent Consultant

Confirms compliance as in AS/NZS 2243.8 and provides the report to F&S.

6

Facilities and Services

Hands over fume exhaust system to the user for acceptance.

Note. All tests must have a favourable result before accepting the fume exhaust system.

  1. Fume cupboards should meet the requirements of AS/NZS 2243.8 Safety in Laboratories - Fume cupboards.

Exception: The minimum discharge height may be reduced to at least one metre above the ridge of a pitched roof or at least 1.8 metres above the deck of a flat roof.

Note: Installations in new buildings should comply with the Australian Standard at the time of construction. Any deviation from the Standard must be approved by WEG.

Fire precautions

  1. Fume exhaust systems are occasionally used for some tasks where there is a significant risk of fire. Risks should be reduced to as low as reasonably practicable (ALARP) at the source following good practise. Controls may include:
  • using minimum quantities of chemicals;
  • condensers on distillation apparatus or for solvent evaporation; and
  • distillation in an inert atmosphere (e.g. under nitrogen).
  1. At the University, a fume exhaust system (a fume cupboard) is not generally fitted with fire detection or suppression systems due to issues with the reliability of components operating in the exhaust stream. At the initial evaluation of the Fume Exhaust System Request Form, the hazard assessment will determine if a fire detection and/or suppression system is required. If required then consider:
  • the technical and practical effectiveness, within such environments with the aim of minimising false alarms and system failures;
  • including a thermal detector. The detector should be linked to the building's emergency control panel, or to a local audible and visible alarm and activate at no more than 60 ºC;
  • being capable of automatically isolating electrical power and flammable gas services to the fume cupboard. A thermocouple or water-flow detector may be suitable for this; or
  • including a misting water sprinkler. The sprinkler head is fitted in the fume cupboard throat to protect the exhaust duct by cooling any hot gases drawn into the exhaust.

Warning: The sprinkler can not be linked to the main sprinkler system.

  • Any fire detection/suppression system should be inspected at least yearly.
  1. The University's Fire Safety Officer must assess fire suppression for new installations and the requirements of the items above.
  2. In buildings with a sprinkler system, a fire sprinkler head should be within one metre of the front of the fume cupboard or within the worker's area.
  3. A fire extinguisher must be available near the work area under AS/NZS2243.8, Section 2.14.3, Fire extinguishers.
  4. The user should act to limit emissions through the proper design and control of the experiment or process. Emissions do not exceed the occupational exposure guidelines.
  5. The Local Area and WHS Branch, WEG may request details of an experiment or process at any time to confirm the emissions don’t exceed the occupational exposure guidelines.
  6. Inspection, testing and maintenance may take one of several forms:
  • periodic cleaning of the fume cupboard by users, regularly and before periodic maintenance;
  • periodic maintenance;
  • performance testing; and
  • specific inspection, testing, and maintenance, especially of filters.

General maintenance principles

  1. The following general maintenance principles apply:
  • general maintenance is the responsibility of F&S, although local areas may take on minor maintenance;
  • before maintenance begins, place a sign near the controls (or on the fume cupboard sash) as ‘system under maintenance’ signage, ensuring the sign is removed when finished;
  • the user removes all chemicals from fume cupboards or where not practicable ensure container caps are closed; and
  • isolate fume cupboards from the power supply to prevent operation; and
  • record all maintenance in the exhaust systems logbook.
    Note: A similar process that meets the aim of protecting workers on the roof and notifying relevant staff\students is also acceptable.

Periodic cleaning of fume cupboards by the users

  1. Regularly and before maintenance operations, fume cupboards must be cleaned to:
  • improve their life and performance; and
  • ensure they are free of risk to users and maintenance staff.
  1. The following protocol applies.

Table 4: Fume exhaust system cleaning protocol

Step

Action

1

Wash the entire interior surface of the work area with detergent solution.

2

When practical, remove the rear baffles (where fitted) to allow thorough cleaning.

3

Where applicable, remove the worktop and thoroughly clean the sump and sink.

4

Clean both sides of sash (if fitted).

5

Wash, rinse and dry all surrounds. Take care around electrical fittings.


Periodic maintenance (six monthly) and performance testing

  1. Use the maintenance schedule and performance testing in Table 5 as a guide for minimum requirements. More frequent maintenance may be required where the fume cupboard is in continual use.

Note: Record all results in the fume exhaust system Logbook.

Table 5: Periodic maintenance and performance testing

Step

Action

1

Inspect and maintain fans, their motors, drives (including belts) and bearings. Lubricate where suitable.

2

Inspect and report on deficient lighting or noise problems.

3

Inspect the fire damper and the release mechanism, if fitted, and replace fusible link, if needed.

4

Check that any air-cleaning device, if fitted, is working properly and maintain if needed.

5

Check and inspect sash cable condition on all cupboards over 1500mm in width.

6

Check the scrubber and wash-down facility, if fitted, is functioning properly.

7

Perform a face velocity test and record the results in the logbook. If problems are obvious then carry out a full smoke test. Conduct the smoke test as described in AS/NZS 2243.8. The laboratory doors must be closed during the tests. Where multiple fume cupboards exist in a room, the remaining fume cupboards should be at a minimum flow position unless otherwise requested.

8

Check the condition of the thermal detector and sprinkler heads, if fitted.

9

Check the scrubber and wash-down facility(if fitted) are functioning properly.

10

Record results of the inspection in the system Logbook and forward a copy of the results to Facilities and Services, Work Environment Group and the Budget Unit.

11

Attach a self-adhesive label to the fume cupboard showing the inspection date, name of inspector, report number and Pass/Fail.

Annual maintenance

  1. Annual maintenance includes periodic maintenance (six-monthly) plus the following.

Table 6: Annual maintenance

Step

Action

1

Remove any baffles to help cleaning. Clean both baffles and rear of the chamber. Cleaning should be performed by an experienced user or under guidance.

Note: Fume cupboards draw through many cubic metres of air per day. This includes dust and experimental debris behind the baffles and in the ductwork, increasing the risk of fire. Because of the difficulty of removal, accessibility, use and condition of various baffles, Budget Unit management may extend the cleaning frequency, but it should not exceed 5 years.

2

Check the condition and satisfactory operation of the fume cupboard system.

3

Check condition of services to the cupboard and ensure that all identified and operational.

4

Check the stability and condition of the discharge stack.

5

Inspect the condition of the exhaust ducting, where possible, the joints and ensure drain points are clear.

6

Check the make-up air balance.

7

Check the operation of the emergency isolator and isolation of services.

8

Check the operation of the low-flow sensor and automatic isolator by changing the airflow conditions to the fume cupboard.

9

Check the condition and operation of the fire control precautions (if fitted).

10

Record results of the inspection in the system Logbook and forward a copy of the results to Facilities and Services, Work Environment Group and Budget Unit.

11

Attach a self-adhesive label to the fume cupboard showing the inspection date, name of inspector, report number and Pass/Fail.


Specific inspection, testing and maintenance

Fume scrubber pH maintenance by F&S and engaged contractors

  1. Where a scrubber is fitted to neutralise acidic\alkaline emissions, it is important to maintain the active solution pH. Use the following protocol to inspect, test, and maintain fume scrubber pH.

Table 7: Fume scrubber testing and maintenance

Step

Action

1

Conduct a hazard assessment and put suitable controls in place to reduce the risk. Wear suitable Personal Protective Equipment (PPE).

2

Before using a fume cupboard, check the scrubber is controlling the expected emissions.

3

For high usage systems, test the pH of the fluid every two to four weeks (or as required) and drain the fluid in the sump to dispose of as per Hazardous waste management protocols.

Note. Clean the system often if indicative from inspections and testing.

4

Replace the fluid and test to ensure the pH level is neutral.

5

Clean and keep the sump as per the manufacturers' specifications.

Note: Wear suitable PPE.

6

Record results in the system's Logbook.

Fume scrubber maintenance by F&S or engaged contractors

  1. The special filter pads in the fume cupboard scrubber should be inspected at least every 12 months. Use the following protocol. For further details refer to the Safe use of wet scrubbers guideline.

Table 8: Scrubber maintenance

Step

Action

1

Conduct a hazard assessment and put suitable controls in place to reduce the risk. Wear suitable PPE.

2

If the filters need cleaning, remove them according to the manufacturer's instructions.

3

Wash the filters thoroughly (in a designated cleaning area 0with detergent and water, and allow them to dry.

Warning: Do not use a high-pressure hose on the pads.

4

Refit the filters according to the manufacturer's instructions and check for leaks.

Note: Replace the filters if damaged.

5

Record results in the system's Logbook.

Carbon Filters

  1. Inspect activated carbon filters (if fitted) at six-monthly intervals (maximum). In cases of constant high-level use of toxic materials, check the system effluent often for contamination. If there is obvious fume and odour breakthrough, notify F&S to install replacement filters.

Non-conforming equipment

  1. Non-conforming fume exhaust systems are those that:
  • fail the smoke test (described as Dangerous in the AS 2243.8); and
  • cannot achieve a face velocity of at least 0.4 m/s under any usable condition.
  1. Any fume exhaust system that does not conform to the specified performance criteria should be tagged or labelled according to danger sign. Before leaving the site the Inspector shall advise the Site Contact of the details of the nonconforming system. WEG should also be notified and if needed advise on any other suitable action.

Summary of results

  1. A summary of the fume exhaust system results are made available to the local area and WEG for information.
  2. Reported results include:
  • face velocity tests, in which the average of the mean velocities from the measurement points are recorded; and
  • smoke tests, to which the following interpretation apply:

Table 9

Result

Description

Good

Smoke travels straight to exhaust without reverse flow or eddies.

Fair

Reverse flow or eddies may be present but not to the extent where the smoke can escape from the confines of the fume cupboard or be blown back over any part of the operator.

Dangerous

Reverse flows or eddies can escape from the confines of the Fume Cupboard or cause the smoke to contact the operator in normal operation. A danger tag shall attached to the exhaust system to prevent its use.

  1. Local areas are to keep the following records for their fume exhaust systems:
  • initial documentation - Request form and site plan;
  • purchase details - System details incorporated in the purchase contract;
  • commissioning documentation (in consultation with F&S);
  • annual and six monthly testing results;
  • logbook; and
  • labels.

Reclassifying

  1. If the proposed use exceeds its current classification, it is the user's responsibility to upgrade (by a formal request to WEG). An interim measure can include access to a suitable exhaust system. Refer to the Fume exhaust system request form.
  2. Where practical, an upgrade of a fume exhaust system may be possible by fitting a cleaning device (filter or scrubber).
  3. When the requirements of the fume exhaust system change to a point where the scrubber or cleaning device is no longer needed, approval is sought from the WEG before the cleaning device can be decommissioned or rendered inoperative.
  4. Label the modified fume exhaust system according to its new classification.

Decommissioning

  1. Where a decommissioned system is not expected to be reactivated in the foreseeable future, the redundant system is removed. This includes the ductwork, fan, scrubber and associated equipment.
  2. Any exhaust system that is no longer required is decommissioned or removed by F&S. The logbook is kept by the local area for a period of no less than five years.
  3. Any fume exhaust system that cannot be brought to the classification required is reclassified, decommissioned or removed.

Incident reporting

  1. All incidents involving the fume exhaust systems at the University are reported via the University's workplace safety incident reporting tool as per the WHS Incident management procedure.

Training obligations/courses

  1. WEG provide chemical safety courses and some local WHS Committees have made these courses compulsory for new chemical users. Local inductions cover chemical safety and management requirements. Refer to WHS Training web page.

Logbooks

  1. Logbooks:
  • inform the user of the fume exhaust system's performance test results and whether the fume cupboard is working satisfactorily;
  • inform maintenance personnel about the system's faults and last repair and user's maintenance and checks; and
  • provide a record of all maintenance work conducted.
  1. A logbook is specific to a particular cupboard. It is located at the fume exhaust system. Information recorded includes:
  • commissioning test results;
  • annual and six monthly performance testing results, which are supplemented by a test report. See Labels Section;
  • repair or other maintenance;
  • fault reports;
  • scheduled cleaning details;
  • wash-down details in perchloric cupboards;
  • scrubber conditions or pH;
  • scrubber drainage date;
  • filter checks; and
  • additional comments.
  1. All of these entries should include the:
  • date; and
  • initials or name of the person making the entry.
  1. Upon the decommissioning of a fume exhaust system, or the completion and filling of a logbook, the logbook shall be kept by the local area for a period of no less than five years.

Labels

  1. There are several labels or signs relevant to or affixed to fume cupboards, including:
  • manufacturer labels;
  • fume cupboard classification labels (for scrubbed, perchloric and special systems);
  • Australian Standard warning label (including spillage containment volume of the fume cupboard); and
  • performance test results label.
  1. The performance test results label indicates whether the system passes the required tests.
  2. A Danger Tag may be affixed to the fume exhaust system. A fume exhaust system under repair is tagged using an "out of service’" and all chemicals and operations in the cupboard are removed. The issuing person is the only person who removes this tag.
  3. In the event of a failed performance test, a "out of service" tag is attached. This tag is only removed by an authorised person after due consideration of the fault. Refer to the Isolation and Danger Tagging Procedure.


Sources

Legal and other requirements

Work Health And Safety Act 2011 (Cth)

Work Health And Safety Regulations 2011 (Cth)

AS/NZS 2243.8:2014 - Safety in laboratories - Fume cupboards

AS/NZS 2243.9:2009 - Safety in laboratories - Recirculating fume cabinets

Information

Printable version (PDF)
Title Managing fume exhaust system
Document Type Procedure
Document Number ANUP_000702
Version
Purpose To define the requirements for managing fume exhaust systems in laboratories at the Australian National University (University).
Audience Staff
Category Administrative
Topic/ SubTopic Health, Safety & Environment - Occupational Health & Safety
 
Effective Date 19 Feb 2018
Next Review Date 31 Dec 2023
 
Responsible Officer: Chief People Officer
Approved By: Chief Operating Officer
Contact Area Safety and Wellbeing
Authority: Work Health and Safety Regulations 2011
Work Health & Safety Act 2011
Delegations 0

Information generated and received by ANU staff in the course of conducting business on behalf of ANU is a record and should be captured by an authorised recordkeeping system. To learn more about University records and recordkeeping practice at ANU, see ANU recordkeeping and Policy: Records and archives management.